The ankle draft model incorporated in ASHRAE Standard 55 was derived from studies in which participants wore summer clothing with exposed ankles (~0.5 clo), potentially leading to overly conservative perimeter heating requirements in winter conditions where office occupants typically wear long trousers, socks, and closed-toe shoes (~0.75 clo). This study evaluated thermal comfort responses to ankle-level draft under such winter clothing conditions through controlled laboratory experiments with 51 participants. Using a within-subjects repeated-measures design, we exposed participants to nine conditions varying supply air temperature (15°C, 17°C, 19°C) and ankle-level air speed (0.1–0.7 m/s) simulating window downdraft while they wore clothing ensembles targeting 0.75 clo.
66
-
67
-
The existing ankle draft model systematically overpredicted dissatisfaction across all conditions. While prior studies with exposed ankles reported dissatisfaction rates of 23–57%, we observed rates of only 6–20%, with the existing model overestimating dissatisfaction by an average of 2.8 times and by as much as 39 percentage points at high air speeds. We fit generalized linear mixed-effects models to data from this study and prior research, developing separate prediction equations for ankle-covered and ankle-uncovered conditions. The covered-ankle model exhibited both a lower baseline dissatisfaction risk and reduced sensitivity to air speed. Whole-body thermal sensation and ankle-level air speed were the only significant predictors; ankle air temperature and room temperature were not significant within the tested ranges.
68
-
69
-
These findings support differentiating ASHRAE Standard 55 ankle draft criteria by clothing insulation level. Adopting a covered-ankle criterion for winter heating scenarios will enable meaningful reductions in perimeter heating requirements without compromising occupant comfort, with associated benefits for installation costs, energy consumption, and carbon emissions.
65
+
The ankle draft model incorporated in ASHRAE Standard 55 was derived
66
+
from studies in which participants wore summer clothing with exposed
67
+
ankles (\~0.5 clo), potentially leading to overly conservative perimeter
68
+
heating requirements in winter conditions where office occupants
69
+
typically wear long trousers, socks, and closed-toe shoes (\~0.75 clo).
70
+
This study evaluated thermal comfort responses to ankle-level draft
71
+
under such winter clothing conditions through controlled laboratory
72
+
experiments with 51 participants. Using a within-subjects
73
+
repeated-measures design, we exposed participants to nine conditions
74
+
varying supply air temperature (15°C, 17°C, 19°C) and ankle-level air
75
+
speed (0.1–0.7 m/s) simulating window downdraft while they wore clothing
76
+
ensembles targeting 0.75 clo.
77
+
78
+
The existing ankle draft model systematically overpredicted
79
+
dissatisfaction across all conditions. While prior studies with exposed
80
+
ankles reported dissatisfaction rates of 23–57%, we observed rates of
81
+
only 6–20%, with the existing model overestimating dissatisfaction by an
82
+
average of 2.8 times and by as much as 39 percentage points at high air
83
+
speeds. We fit generalized linear mixed-effects models to data from this
84
+
study and prior research, developing separate prediction equations for
85
+
ankle-covered and ankle-uncovered conditions. The covered-ankle model
86
+
exhibited both a lower baseline dissatisfaction risk and reduced
87
+
sensitivity to air speed. Whole-body thermal sensation and ankle-level
88
+
air speed were the only significant predictors; ankle air temperature
89
+
and room temperature were not significant within the tested ranges.
90
+
91
+
These findings support differentiating ASHRAE Standard 55 ankle draft
92
+
criteria by clothing insulation level. Adopting a covered-ankle
93
+
criterion for winter heating scenarios will enable meaningful reductions
94
+
in perimeter heating requirements without compromising occupant comfort,
95
+
with associated benefits for installation costs, energy consumption, and
96
+
carbon emissions.
70
97
71
98
# Introduction
72
99
@@ -164,7 +191,13 @@ whole-body thermal sensation of approximately −0.5 (slightly cool) on
164
191
the ASHRAE seven-point scale as calculated using the CBE Comfort Tool
165
192
[@tartariniCBEThermalComfort2020].
166
193
167
-
{#fig-setup
194
+
![Experimental configuration and temporal protocol: (a) Seated occupant
195
+
positioned 0.7 m from the custom displacement diffuser, which simulates
196
+
window downdraft by directing conditioned air toward the ankle region
197
+
from behind; (b) Timeline of the 120-minute experimental sessions
198
+
featuring overlapping participant groups and synchronized questionnaire
199
+
intervals to characterize the progression of local and whole-body
In addition, as shown in @fig-model-comp(b), the model retained
789
-
acceptable discrimination on this dataset (AUC =
790
-
`r sprintf("%.3f", liu_calibration_stats["C (ROC)"])`), the calibration
791
-
results indicated a systematic overestimation under winter conditions.
792
-
Across the nine experimental conditions, the mean observed
793
-
dissatisfaction rate was `r liu_model_summary$mean_observed`%, whereas
794
-
the Liu model predicted an average of
795
-
`r liu_model_summary$mean_predicted`%, corresponding to an
796
-
overestimation of approximately
797
-
`r liu_model_summary$overprediction_ratio` times. The discrepancy was
798
-
greatest at `r liu_max_diff_speed` air speed and smaller, but still
799
-
evident, at `r liu_min_diff_speed` air speed.
815
+
magnitude of model overestimation); (b) calibration curve of the existing model on this study dataset.](figs/model_error_combined.png){#fig-model-comp width="90%"}
816
+
817
+
In addition, we evaluated the performance of the existing ankle draft model by fitting its predictions—based on local air speed and whole-body thermal sensation—against our observed binary satisfaction outcomes using logistic regression. The resulting calibration curve is shown in @fig-model-comp(b). In a well-calibrated model, the curve should closely follow the 45° ideal line; however, our results show the curve located predominantly below this line.
818
+
819
+
While the model maintained acceptable discriminative ability (AUC = 0.77), meaning it can effectively rank which conditions are more likely to cause discomfort, the calibration statistics reveal significant inaccuracy in the magnitude of its predictions. With a Brier score of 0.14 and a systematic shift away from the ideal line, the results confirm that the existing model consistently overestimates the probability of ankle draft dissatisfaction under winter conditions.
0 commit comments