‎manuscript/index.qmd‎

Lines changed: 73 additions & 44 deletions
Original file line numberDiff line numberDiff line change
@@ -62,11 +62,38 @@ source(here::here("src", "R", "x_analysis.R"))
6262

6363
# Abstract {.unnumbered}
6464

65-
The ankle draft model incorporated in ASHRAE Standard 55 was derived from studies in which participants wore summer clothing with exposed ankles (~0.5 clo), potentially leading to overly conservative perimeter heating requirements in winter conditions where office occupants typically wear long trousers, socks, and closed-toe shoes (~0.75 clo). This study evaluated thermal comfort responses to ankle-level draft under such winter clothing conditions through controlled laboratory experiments with 51 participants. Using a within-subjects repeated-measures design, we exposed participants to nine conditions varying supply air temperature (15°C, 17°C, 19°C) and ankle-level air speed (0.1–0.7 m/s) simulating window downdraft while they wore clothing ensembles targeting 0.75 clo.
66-
67-
The existing ankle draft model systematically overpredicted dissatisfaction across all conditions. While prior studies with exposed ankles reported dissatisfaction rates of 23–57%, we observed rates of only 6–20%, with the existing model overestimating dissatisfaction by an average of 2.8 times and by as much as 39 percentage points at high air speeds. We fit generalized linear mixed-effects models to data from this study and prior research, developing separate prediction equations for ankle-covered and ankle-uncovered conditions. The covered-ankle model exhibited both a lower baseline dissatisfaction risk and reduced sensitivity to air speed. Whole-body thermal sensation and ankle-level air speed were the only significant predictors; ankle air temperature and room temperature were not significant within the tested ranges.
68-
69-
These findings support differentiating ASHRAE Standard 55 ankle draft criteria by clothing insulation level. Adopting a covered-ankle criterion for winter heating scenarios will enable meaningful reductions in perimeter heating requirements without compromising occupant comfort, with associated benefits for installation costs, energy consumption, and carbon emissions.
65+
The ankle draft model incorporated in ASHRAE Standard 55 was derived
66+
from studies in which participants wore summer clothing with exposed
67+
ankles (\~0.5 clo), potentially leading to overly conservative perimeter
68+
heating requirements in winter conditions where office occupants
69+
typically wear long trousers, socks, and closed-toe shoes (\~0.75 clo).
70+
This study evaluated thermal comfort responses to ankle-level draft
71+
under such winter clothing conditions through controlled laboratory
72+
experiments with 51 participants. Using a within-subjects
73+
repeated-measures design, we exposed participants to nine conditions
74+
varying supply air temperature (15°C, 17°C, 19°C) and ankle-level air
75+
speed (0.1–0.7 m/s) simulating window downdraft while they wore clothing
76+
ensembles targeting 0.75 clo.
77+
78+
The existing ankle draft model systematically overpredicted
79+
dissatisfaction across all conditions. While prior studies with exposed
80+
ankles reported dissatisfaction rates of 23–57%, we observed rates of
81+
only 6–20%, with the existing model overestimating dissatisfaction by an
82+
average of 2.8 times and by as much as 39 percentage points at high air
83+
speeds. We fit generalized linear mixed-effects models to data from this
84+
study and prior research, developing separate prediction equations for
85+
ankle-covered and ankle-uncovered conditions. The covered-ankle model
86+
exhibited both a lower baseline dissatisfaction risk and reduced
87+
sensitivity to air speed. Whole-body thermal sensation and ankle-level
88+
air speed were the only significant predictors; ankle air temperature
89+
and room temperature were not significant within the tested ranges.
90+
91+
These findings support differentiating ASHRAE Standard 55 ankle draft
92+
criteria by clothing insulation level. Adopting a covered-ankle
93+
criterion for winter heating scenarios will enable meaningful reductions
94+
in perimeter heating requirements without compromising occupant comfort,
95+
with associated benefits for installation costs, energy consumption, and
96+
carbon emissions.
7097

7198
# Introduction
7299

@@ -164,7 +191,13 @@ whole-body thermal sensation of approximately −0.5 (slightly cool) on
164191
the ASHRAE seven-point scale as calculated using the CBE Comfort Tool
165192
[@tartariniCBEThermalComfort2020].
166193

167-
![Experimental configuration and temporal protocol: (a) Seated occupant positioned 0.7 m from the custom displacement diffuser, which simulates window downdraft by directing conditioned air toward the ankle region from behind; (b) Timeline of the 120-minute experimental sessions featuring overlapping participant groups and synchronized questionnaire intervals to characterize the progression of local and whole-body thermal perception.](figs/experimental_setup.png){#fig-setup
194+
![Experimental configuration and temporal protocol: (a) Seated occupant
195+
positioned 0.7 m from the custom displacement diffuser, which simulates
196+
window downdraft by directing conditioned air toward the ankle region
197+
from behind; (b) Timeline of the 120-minute experimental sessions
198+
featuring overlapping participant groups and synchronized questionnaire
199+
intervals to characterize the progression of local and whole-body
200+
thermal perception.](figs/experimental_setup.png){#fig-setup
168201
width="75%"}
169202

170203
We used custom displacement diffusers to deliver conditioned air to the
@@ -305,7 +338,7 @@ calibration intercept and slope, AUC, and Brier score. All analyses were
305338
implemented using the R package CalibrationCurves
306339
[@deCockCalibrationCurves2023].
307340

308-
### Development of the new ankle draft model
341+
### Development of the new ankle draft model {#sec-method-new-model}
309342

310343
We modeled ankle draft dissatisfaction using a generalized linear mixed
311344
model with a binomial distribution and logit link, as the outcome was
@@ -732,7 +765,7 @@ intensified as air speed increased, with the most significant
732765
temperature drops occurring when moving from low to medium
733766
airflow.](figs/tsk_p.png){#fig-tsk width="90%"}
734767

735-
## Dissatisfaction with ankle draft
768+
## Dissatisfaction with ankle draft {#sec-model-comp}
736769

737770
```{r}
738771
#| label: setup-results-data
@@ -779,24 +812,11 @@ pp.
779812
(a) The model consistently overpredicted ankle-level dissatisfaction
780813
across all conditions, with discrepancies widening at higher air speeds
781814
(points represent mean values, with the segment length indicating the
782-
magnitude of model overestimation); (b) while maintaining acceptable
783-
discrimination (AUC =
784-
`r sprintf("%.2f", liu_calibration_stats["C (ROC)"])`), the calibration
785-
curve confirms a systematic overestimation of dissatisfaction in winter
786-
conditions.](figs/model_error_combined.png){#fig-model-comp width="90%"}
787-
788-
In addition, as shown in @fig-model-comp(b), the model retained
789-
acceptable discrimination on this dataset (AUC =
790-
`r sprintf("%.3f", liu_calibration_stats["C (ROC)"])`), the calibration
791-
results indicated a systematic overestimation under winter conditions.
792-
Across the nine experimental conditions, the mean observed
793-
dissatisfaction rate was `r liu_model_summary$mean_observed`%, whereas
794-
the Liu model predicted an average of
795-
`r liu_model_summary$mean_predicted`%, corresponding to an
796-
overestimation of approximately
797-
`r liu_model_summary$overprediction_ratio` times. The discrepancy was
798-
greatest at `r liu_max_diff_speed` air speed and smaller, but still
799-
evident, at `r liu_min_diff_speed` air speed.
815+
magnitude of model overestimation); (b) calibration curve of the existing model on this study dataset.](figs/model_error_combined.png){#fig-model-comp width="90%"}
816+
817+
In addition, we evaluated the performance of the existing ankle draft model by fitting its predictions—based on local air speed and whole-body thermal sensation—against our observed binary satisfaction outcomes using logistic regression. The resulting calibration curve is shown in @fig-model-comp(b). In a well-calibrated model, the curve should closely follow the 45° ideal line; however, our results show the curve located predominantly below this line.
818+
819+
While the model maintained acceptable discriminative ability (AUC = 0.77), meaning it can effectively rank which conditions are more likely to cause discomfort, the calibration statistics reveal significant inaccuracy in the magnitude of its predictions. With a Brier score of 0.14 and a systematic shift away from the ideal line, the results confirm that the existing model consistently overestimates the probability of ankle draft dissatisfaction under winter conditions.
800820

801821
## Updated model for winter conditions
802822

@@ -902,15 +922,22 @@ model_final_table <- dplyr::bind_rows(
902922
dplyr::select(model_display, term_label, estimate_fmt, std_error_fmt, z_value_fmt, p_value_fmt)
903923
```
904924

905-
As shown in @tbl-updated-model-screening, in the mixed-effects model
906-
including all candidate predictors, air speed at ankle, whole-body
907-
thermal sensation, and ankle condition were significantly associated
908-
with draft dissatisfaction at the ankle, whereas room air temperature,
909-
air temperature at ankle, and turbulence intensity were not significant
910-
within the range investigated in this study. Based on these results,
911-
separate mixed-effects models for ankle draft dissatisfaction were
912-
developed for the ankle-uncovered and ankle-covered conditions, using
913-
air speed at ankle and whole-body thermal sensation as predictors.
925+
As shown in @sec-model-comp, the existing model showed limited accuracy
926+
in predicting ankle draft dissatisfaction under winter conditions. This
927+
highlights the need for a revised model that accounts for differences in
928+
application contexts. To enable an integrated analysis of the effects of
929+
different factors on ankle draft dissatisfaction, we combined data from
930+
@liuPredictedPercentageDissatisfied2017 and collected in this study
931+
in the modeling dataset. To identify significant predictors, a model
932+
including all candidate predictors was first fitted following the
933+
methods described in @sec-method-new-model. Given that both datasets
934+
were obtained from repeated measurements, subject-level dependence was
935+
accounted for in the analysis. The result of the screening model is
936+
shown in @tbl-updated-model-screening. Ankle-level air speed, whole-body
937+
thermal sensation, and ankle condition were significantly correlated
938+
with ankle draft dissatisfaction, whereas room air temperature,
939+
ankle-level air temperature, and turbulence intensity were not
940+
significant within the range investigated in this study.
914941

915942
```{r}
916943
#| label: tbl-updated-model-screening
@@ -934,15 +961,17 @@ knitr::kable(
934961
)
935962
```
936963

937-
As shown in @tbl-updated-model-final, the two final models exhibited the
938-
same structure but different coefficients. The intercept of the covered
939-
model was `r sprintf("%.2f", abs(glmm_delta_intercept))` units lower
940-
than that of the uncovered model, indicating a substantially lower
941-
baseline risk of ankle draft dissatisfaction when the ankle was covered
942-
by clothing. In addition, the air speed coefficient was smaller in the
943-
covered model than in the uncovered model, indicating reduced
944-
sensitivity of dissatisfaction to air velocity under ankle-covered
945-
conditions.
964+
Based on these results, separate mixed-effects models for ankle draft
965+
dissatisfaction were developed for the ankle-uncovered and ankle-covered
966+
conditions, using ankle-level air speed and whole-body thermal sensation
967+
as predictors. As shown in @tbl-updated-model-final, the two final
968+
models exhibited the same structure but different coefficients. The
969+
intercept of the covered model was 1.91 units lower than that of the
970+
uncovered model, indicating a lower baseline risk of ankle draft
971+
dissatisfaction when the ankle was covered by clothing. In addition, the
972+
air speed coefficient was smaller in the covered model than in the
973+
uncovered model, indicating reduced sensitivity of dissatisfaction to
974+
air speed under ankle-covered conditions.
946975

947976
For the ankle-uncovered condition, the approximate closed-form equation
948977
derived from the marginal predictions of the mixed-effects model can be

0 commit comments